DTMn-K5 and DTMn-K11 enclosed direct motorstarter 2022-07-12T14:15:24+00:00

DTMn-K5 and DTMn-K11 enclosed direct motorstarter

Inside enclosure are available 1 pc DL-K5 or DL-K11 contactor, 1 pc H0-2K thermal relay, 2 pcs push-buttons, 1 pc earth terminal and wiring.

Switchable rated motor-power [kW]

DTMn-K5

  • AC-2 and AC-3 230 V: 3 kW
  • AC-2 and AC-3 400 V: 6,5 kW
  • AC-2 and AC-3 500 V: 7,5 kW
  • AC-4 400 V: 4 kW

DTMn-K11

  • AC-2 and AC-3 230 V: 5,5 kW
  • AC-2 and AC-3 400 V: 11 kW
  • AC-2 and AC-3 500 V: 15 kW
  • AC-4 400 V: 5,5 kW

Characteristics

  • Device can be loaded to 20 A max!
  • Connection across stuffing box of the vessel
  • Mounting 2 pcs M5×20 screws (attached)
  • Dimensions: 126×192×124 mm

Using

Direct motorstarter

Degree of protection: IP 54

Relevant standard: EN 60947-4-1

Downloadable document

     THERMAL RELAYS, MOTORSTARTERS

More information